Gross rated electrical power
85 kW
Nominal electrical power net
80 kW
Maximum usable rated thermal output
198 kW
Freely adjustable electrical power range
50 - 85 kW
Typical operating hours per year
> 8.000 h
Consumption of wood chips per year
approx. 550 t (atro)

Technical data
LiPRO HGW300

Dimensions of the gasworks
Length
6,935 mm
Width
1,821 mm
Height
approx. 2,881 mm
Weight of the gas plant
Weight
approx. 5,000 kg
Minimum dimensions of the installation area of the gasworks
Length incl. minimum maintenance area
7,480 mm
Width incl. minimum maintenance area
2,400 mm
Height incl. maintenance area for pyrolysis screw
approx. 5,500 mm

A height of approx. 5.5 m is required above the pyrolysis screw (only there, not everywhere) for maintenance of the gasworks. If this room height is not available, it is recommended to provide a corresponding opening in the ceiling.

Fuel
Natural wood chips
P45 Size/standard
Water content
< W10 m-%
Fine fraction
< 5 m-%
Fuel consumption (atro) / kilowatt hour electric
0.8 kg/kWh
Ash/coal volume
0.4 - 1 (0.6 - 1.4) kg/h (m-%)
Wood gas composition
Hydrogen
18.3 % by volume
Carbon monoxide
21 % by volume
Methane
1.6 % by volume
Carbon dioxide
11.8% by volume
Nitrogen
47.3% by volume
Calorific value
5.1 MJ/Nm3

The proportions of the wood gas composition can fluctuate by several percentage points depending on the operating status.

Technical data
LiPRO HGM300

Dimensions of the CHP unit
Length
2,712 mm
Width
approx. 1,400 mm
Height without feet
1,972 mm
Height with extensions
approx. 2,100 mm
Weight of the CHP unit
Weight
approx. 2,000 kg
bhkw
Minimum dimensions of the installation area of the CHP unit
Length incl. maintenance area
approx. 4,100 mm
Width incl. maintenance area
approx. 2,430 mm
Key technical data of the CHP unit
Cylinder
6 pcs.
Displacement
8,4 l
Gross rated electrical power
85 kW
Nominal electrical power net
80 kW
Usable thermal output (incl. heat from HGW300)
198 kW
Gross electrical power range
50 - 85 kW
Flow temperature (by module)
85 - 100 °C (100 °C with option: high temperature)
Return temperature (before module)
65 °C

Technical data
LiPRO E-Control 300

Dimensions of the control cabinet
Height
2,200 mm
Width
1,200 mm
Depth
550 mm

Technical data
LiPRO HGF200/300

Dimensions of the gas flare
Height
3,169 mm
Width
600 mm
Diameter
811 mm
Weight of the gas flare
Weight
approx. 150 kg